CVE-2019-6845 1 Schneider-electric 46 Modicon M340, Modicon M340 Firmware, Modicon M580 and 43 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists in Modicon M580, Modicon M340, Modicon Premium , Modicon Quantum (all firmware versions), which could cause the disclosure of information when transferring applications to the controller using Modbus TCP protocol.
CVE-2019-6844 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.0 MEDIUM 4.9 MEDIUM
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service atack on the PLC when upgrading the controller with a firmware package containing an invalid web server image using FTP protocol.
CVE-2019-6843 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.0 MEDIUM 4.9 MEDIUM
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 with firmware (version prior to V3.10), Modicon M340 (all firmware versions), and Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the controller with an empty firmware package using FTP protocol.
CVE-2019-6842 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.0 MEDIUM 4.9 MEDIUM
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the firmware with a missing web server image inside the package using FTP protocol.
CVE-2019-6841 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.0 MEDIUM 4.9 MEDIUM
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 with firmware (version prior to V3.10), Modicon M340 (all firmware versions), and Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the firmware with no firmware image inside the package using FTP protocol.
CVE-2019-6840 1 Schneider-electric 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
A Format String: CWE-134 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow an attacker to send a crafted message to the target server, thereby causing arbitrary commands to be executed.
CVE-2019-6839 1 Schneider-electric 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more 2024-11-21 6.5 MEDIUM 8.8 HIGH
A CWE-434: Unrestricted Upload of File with Dangerous Type vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow a user with low privileges to upload a rogue file.
CVE-2019-6838 1 Schneider-electric 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more 2024-11-21 5.5 MEDIUM 6.5 MEDIUM
A CWE-863: Incorrect Authorization vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow a user with low privileges to delete a critical file.
CVE-2019-6837 1 Schneider-electric 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more 2024-11-21 6.4 MEDIUM 9.1 CRITICAL
A Server-Side Request Forgery (SSRF): CWE-918 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could cause server configuration data to be exposed when an attacker modifies a URL.
CVE-2019-6836 1 Schneider-electric 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-863: Incorrect Authorization vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow the file system to access the wrong file.
CVE-2019-6835 1 Schneider-electric 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more 2024-11-21 3.5 LOW 5.4 MEDIUM
A Cross-Site Scripting (XSS) CWE-79 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow an attacker to inject client-side script when a user visits a web page.
CVE-2019-6834 1 Schneider-electric 1 Software Update 2024-11-21 9.3 HIGH 7.3 HIGH
A CWE-502: Deserialization of Untrusted Data vulnerability exists which could allow an attacker to execute arbitrary code on the targeted system with SYSTEM privileges when placing a malicious user to be authenticated for this vulnerability to be successfully exploited. Affected Product: Schneider Electric Software Update (SESU) SUT Service component (V2.1.1 to V2.3.0)
CVE-2019-6832 1 Schneider-electric 4 Lss100100, Lss100200, Spacelynk Firmware and 1 more 2024-11-21 6.8 MEDIUM 8.3 HIGH
A CWE-287: Authentication vulnerability exists in spaceLYnk (all versions before 2.4.0) and Wiser for KNX (all versions before 2.4.0 - formerly known as homeLYnk), which could cause loss of control when an attacker bypasses the authentication.
CVE-2019-6831 1 Schneider-electric 2 Bmxnor0200h, Bmxnor0200h Firmware 2024-11-21 5.0 MEDIUM 8.6 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause disconnection of active connections when an unusually high number of IEC 60870- 5-104 packets are received by the module on port 2404/TCP.
CVE-2019-6830 1 Schneider-electric 2 Modicon M580, Modicon M580 Firmware 2024-11-21 7.1 HIGH 5.9 MEDIUM
A CWE-248: Uncaught Exception vulnerability exists IN Modicon M580 all versions prior to V2.80, which could cause a possible denial of service when sending an appropriately timed HTTP request to the controller.
CVE-2019-6829 1 Schneider-electric 4 Modicon M340, Modicon M340 Firmware, Modicon M580 and 1 more 2024-11-21 7.8 HIGH 7.5 HIGH
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus.
CVE-2019-6828 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 7.8 HIGH 7.5 HIGH
A CWE-248: Uncaught Exception vulnerability exists Modicon M580 (firmware version prior to V2.90), Modicon M340 (firmware version prior to V3.10), Modicon Premium (all versions), and Modicon Quantum (all versions), which could cause a possible denial of service when reading specific coils and registers in the controller over Modbus.
CVE-2019-6827 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 6.8 MEDIUM 7.8 HIGH
A CWE-787: Out-of-bounds Write vulnerability exists in Interactive Graphical SCADA System (IGSS), Version 14 and prior, which could cause a software crash when data in the mdb database is manipulated.
CVE-2019-6826 1 Schneider-electric 1 Somachine Hvac 2024-11-21 6.8 MEDIUM 7.8 HIGH
A CWE-426: Untrusted Search Path vulnerability exists in SoMachine HVAC v2.4.1 and earlier versions, which could cause arbitrary code execution on the system running SoMachine HVAC when a malicious DLL library is loaded by the product.
CVE-2019-6825 1 Schneider-electric 1 Proclima 2024-11-21 6.8 MEDIUM 7.8 HIGH
A CWE-427: Uncontrolled Search Path Element vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow a malicious DLL file, with the same name of any resident DLLs inside the software installation, to execute arbitrary code in all versions of ProClima prior to version 8.0.0.
CVE-2019-6824 1 Schneider-electric 1 Proclima 2024-11-21 10.0 HIGH 9.8 CRITICAL
A CWE-119: Buffer Errors vulnerability exists in ProClima (all versions prior to version 8.0.0) which allows an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
CVE-2019-6823 1 Schneider-electric 1 Proclima 2024-11-21 10.0 HIGH 9.8 CRITICAL
A CWE-94: Code Injection vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow an unauthenticated, remote attacker to execute arbitrary code on the targeted system in all versions of ProClima prior to version 8.0.0.
CVE-2019-6822 1 Schneider-electric 1 Zelio Soft 2 2024-11-21 6.8 MEDIUM 7.8 HIGH
A Use After Free: CWE-416 vulnerability exists in Zelio Soft 2, V5.2 and earlier, which could cause remote code execution when opening a specially crafted Zelio Soft 2 project file.
CVE-2019-6821 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 6.4 MEDIUM 6.5 MEDIUM
CWE-330: Use of Insufficiently Random Values vulnerability, which could cause the hijacking of the TCP connection when using Ethernet communication in Modicon M580 firmware versions prior to V2.30, and all firmware versions of Modicon M340, Modicon Premium, Modicon Quantum.
CVE-2019-6820 1 Schneider-electric 24 Atv Imc Drive Controller, Atv Imc Drive Controller Firmware, Modicon Lmc058 and 21 more 2024-11-21 6.4 MEDIUM 8.2 HIGH
A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is received in all versions of: Modicon M100, Modicon M200, Modicon M221, ATV IMC drive controller, Modicon M241, Modicon M251, Modicon M258, Modicon LMC058, Modicon LMC078, PacDrive Eco ,PacDrive Pro, PacDrive Pro2
CVE-2019-6819 1 Schneider-electric 38 Bmeh582040, Bmeh582040c, Bmeh584040 and 35 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium.
CVE-2019-6816 1 Schneider-electric 2 Modicon Quantum, Modicon Quantum Firmware 2024-11-21 6.4 MEDIUM 9.1 CRITICAL
In Modicon Quantum all firmware versions, a CWE-94: Code Injection vulnerability could cause an unauthorized firmware modification with possible Denial of Service when using Modbus protocol.
CVE-2019-6815 1 Schneider-electric 2 Modicon Quantum, Modicon Quantum Firmware 2024-11-21 6.4 MEDIUM 9.1 CRITICAL
In Modicon Quantum all firmware versions, CWE-264: Permissions, Privileges, and Access Control vulnerabilities could cause a denial of service or unauthorized modifications of the PLC configuration when using Ethernet/IP protocol.
CVE-2019-6814 1 Schneider-electric 14 Net5500, Net5500 Firmware, Net5501 and 11 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
A CWE-287: Improper Authentication vulnerability exists in the NET55XX Encoder with firmware prior to version 2.1.9.7 which could cause impact to confidentiality, integrity, and availability when a remote attacker crafts a malicious request to the encoder webUI.
CVE-2019-6813 1 Schneider-electric 4 Bmxnor0200h, Bmxnor0200h Firmware, Modicon M340 and 1 more 2024-11-21 7.8 HIGH 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions) and Modicon M340 controller (all firmware versions), which could cause denial of service when truncated SNMP packets on port 161/UDP are received by the device.
CVE-2019-6812 1 Schneider-electric 2 Bmx-nor-0200h, Bmx-nor-0200h Firmware 2024-11-21 4.0 MEDIUM 7.2 HIGH
A CWE-798 use of hardcoded credentials vulnerability exists in BMX-NOR-0200H with firmware versions prior to V1.7 IR 19 which could cause a confidentiality issue when using FTP protocol.
CVE-2019-6811 1 Schneider-electric 4 Modicon Quantum 140noe77101, Modicon Quantum 140noe77101 Firmware, Modicon Quantum 140noe77111 and 1 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
An Improper Check for Unusual or Exceptional Conditions (CWE-754) vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a power cycle to recover.
CVE-2019-6810 1 Schneider-electric 2 Bmxnor0200h, Bmxnor0200h Firmware 2024-11-21 6.5 MEDIUM 8.8 HIGH
CWE-284: Improper Access Control vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause the execution of commands by unauthorized users when using IEC 60870-5-104 protocol.
CVE-2019-6809 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 7.8 HIGH 7.5 HIGH
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware versions prior to V2.90), Modicon M340 (firmware versions prior to V3.10), Modicon Premium (all versions), Modicon Quantum (all versions), which could cause a possible denial of service when reading invalid data from the controller.
CVE-2019-6808 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a remote code execution by overwriting configuration settings of the controller over Modbus.
CVE-2019-6807 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a possible denial of service when writing sensitive application variables to the controller over Modbus.
CVE-2019-6806 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-200: Information Exposure vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of SNMP information when reading variables in the controller using Modbus.
CVE-2019-10981 1 Schneider-electric 2 Citectscada, Scada Expert Vijeo Citect 2024-11-21 2.1 LOW 7.8 HIGH
In Vijeo Citect 7.30 and 7.40, and CitectSCADA 7.30 and 7.40, a vulnerability has been identified that may allow an authenticated local user access to Citect user credentials.
CVE-2019-10953 5 Abb, Phoenixcontact, Schneider-electric and 2 more 20 Pm554-tp-eth, Pm554-tp-eth Firmware, Ilc 151 Eth and 17 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.
CVE-2018-8872 1 Schneider-electric 2 Triconex Tricon Mp 3008, Triconex Tricon Mp 3008 Firmware 2024-11-21 9.3 HIGH 8.1 HIGH
In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, system calls read directly from memory addresses within the control program area without any verification. Manipulating this data could allow attacker data to be copied anywhere within memory.