Filtered by vendor Schneider-electric
Subscribe
Filtered by product Modicon M340 Bmxp342020
Subscribe
Total
39 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2014-0754 | 1 Schneider-electric | 86 171ccc96020, 171ccc96020 Firmware, 171ccc96020c and 83 more | 2025-08-26 | 10.0 HIGH | N/A |
|
Directory traversal vulnerability in SchneiderWEB on Schneider Electric Modicon PLC Ethernet modules 140CPU65x Exec before 5.5, 140NOC78x Exec before 1.62, 140NOE77x Exec before 6.2, BMXNOC0401 before 2.05, BMXNOE0100 before 2.9, BMXNOE0110x Exec before 6.0, TSXETC101 Exec before 2.04, TSXETY4103x Exec before 5.7, TSXETY5103x Exec before 5.9, TSXP57x ETYPort Exec before 5.7, and TSXP57x Ethernet Copro Exec before 5.5 allows remote attackers to visit arbitrary resources via a crafted HTTP request ...
Show More |
|||||
| CVE-2017-6017 | 1 Schneider-electric | 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more | 2025-04-20 | 7.8 HIGH | 7.5 HIGH |
|
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
|
|||||
| CVE-2015-7937 | 1 Schneider-electric | 13 Bmxnoc0401, Bmxnoe0100, Bmxnoe0100h and 10 more | 2025-04-12 | 10.0 HIGH | N/A |
|
Stack-based buffer overflow in the GoAhead Web Server on Schneider Electric Modicon M340 PLC BMXNOx and BMXPx devices allows remote attackers to execute arbitrary code via a long password in HTTP Basic Authentication data.
|
|||||
| CVE-2013-2763 | 1 Schneider-electric | 24 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 21 more | 2025-04-11 | 5.0 MEDIUM | N/A |
|
The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions.
|
|||||
| CVE-2023-6408 | 1 Schneider-electric | 90 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 87 more | 2025-01-23 | N/A | 8.1 HIGH |
|
CWE-924: Improper Enforcement of Message Integrity During Transmission in a
Communication Channel vulnerability exists that could cause a denial of service and loss of
confidentiality, integrity of controllers when conducting a Man in the Middle attack.
|
|||||
| CVE-2022-45789 | 1 Schneider-electric | 72 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 69 more | 2024-11-21 | N/A | 8.1 HIGH |
|
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)
|
|||||
| CVE-2022-45788 | 1 Schneider-electric | 108 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 105 more | 2024-11-21 | N/A | 7.5 HIGH |
|
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - pa ...
Show More |
|||||
| CVE-2022-37300 | 1 Schneider-electric | 70 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 67 more | 2024-11-21 | N/A | 9.8 CRITICAL |
|
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU ...
Show More |
|||||
| CVE-2022-0222 | 1 Schneider-electric | 28 Modicon M340 Bmxnoe0100, Modicon M340 Bmxnoe0100 Firmware, Modicon M340 Bmxnoe0110 and 25 more | 2024-11-21 | N/A | 7.5 HIGH |
|
A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24)
|
|||||
| CVE-2021-22792 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert ...
Show More |
|||||
| CVE-2021-22791 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2024-11-21 | 4.0 MEDIUM | 6.5 MEDIUM |
|
A CWE-787: Out-of-bounds Write vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, inc ...
Show More |
|||||
| CVE-2021-22790 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2024-11-21 | 4.0 MEDIUM | 6.5 MEDIUM |
|
A CWE-125: Out-of-bounds Read vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, incl ...
Show More |
|||||
| CVE-2021-22789 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2024-11-21 | 4.0 MEDIUM | 6.5 MEDIUM |
|
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions) ...
Show More |
|||||
| CVE-2021-22788 | 1 Schneider-electric | 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-787: Out-of-bounds Write vulnerability exists that could cause denial of service when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum ...
Show More |
|||||
| CVE-2021-22787 | 1 Schneider-electric | 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions ...
Show More |
|||||
| CVE-2021-22786 | 1 Schneider-electric | 82 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 79 more | 2024-11-21 | N/A | 7.5 HIGH |
|
A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum ...
Show More |
|||||
| CVE-2021-22785 | 1 Schneider-electric | 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-200: Information Exposure vulnerability exists that could cause sensitive information of files located in the web root directory to leak when an attacker sends a HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP5 ...
Show More |
|||||
| CVE-2021-22779 | 1 Schneider-electric | 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more | 2024-11-21 | 6.4 MEDIUM | 9.1 CRITICAL |
|
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read ...
Show More |
|||||
| CVE-2020-7549 | 1 Schneider-electric | 38 140cpu65150, 140cpu65150 Firmware, 140noc78000 and 35 more | 2024-11-21 | 5.0 MEDIUM | 5.3 MEDIUM |
|
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause denial of HTTP and FTP services when a series of specially crafted requests is sent to the controller over HTTP.
|
|||||
| CVE-2020-7543 | 1 Schneider-electric | 32 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 29 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
|
|||||
| CVE-2020-7542 | 1 Schneider-electric | 40 140cpu65150, 140cpu65150 Firmware, Modicon M340 Bmxp341000 and 37 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
|
|||||
| CVE-2020-7541 | 1 Schneider-electric | 40 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 37 more | 2024-11-21 | 5.0 MEDIUM | 5.3 MEDIUM |
|
A CWE-425: Direct Request ('Forced Browsing') vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of sensitive data when sending a specially crafted request to the controller over HTTP.
|
|||||
| CVE-2020-7540 | 1 Schneider-electric | 46 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 43 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
|
A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.
|
|||||
| CVE-2020-7539 | 1 Schneider-electric | 40 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 37 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP.
|
|||||
| CVE-2020-7537 | 1 Schneider-electric | 38 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 35 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
|
|||||
| CVE-2020-7536 | 1 Schneider-electric | 20 Bmxnoe0100, Bmxnoe0100 Firmware, Bmxnoe0110 and 17 more | 2024-11-21 | 7.8 HIGH | 7.5 HIGH |
|
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP.
|
|||||
| CVE-2020-7535 | 1 Schneider-electric | 42 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 39 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
|
|||||
| CVE-2020-7534 | 1 Schneider-electric | 20 140cpu65, 140cpu65 Firmware, 140noc78000 and 17 more | 2024-11-21 | 6.8 MEDIUM | 8.8 HIGH |
|
A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists on the web server used, that could cause a leak of sensitive data or unauthorized actions on the web server during the time the user is logged in. Affected Products: Modicon M340 CPUs: BMXP34 (All Versions), Modicon Quantum CPUs with integrated Ethernet (Copro): 140CPU65 (All Versions), Modicon Premium CPUs with integrated Ethernet (Copro): TSXP57 (All Versions), Modicon M340 ethernet modules: (BMXNOC0401, BMXNOE01, BMXNOR0200H) ( ...
Show More |
|||||
| CVE-2019-6855 | 1 Schneider-electric | 44 Ecostruxure Control Expert, Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware and 41 more | 2024-11-21 | 7.5 HIGH | 7.3 HIGH |
|
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.
|
|||||
| CVE-2019-6819 | 1 Schneider-electric | 38 Bmeh582040, Bmeh582040c, Bmeh584040 and 35 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium.
|
|||||
| CVE-2018-7851 | 1 Schneider-electric | 41 140cra312xxx, 140cra312xxx Firmware, Bmeh582040 and 38 more | 2024-11-21 | 6.8 MEDIUM | 6.5 MEDIUM |
|
CWE-119: Buffer errors vulnerability exists in Modicon M580 with firmware prior to V2.50, Modicon M340 with firmware prior to V3.01, BMxCRA312xx with firmware prior to V2.40, All firmware versions of Modicon Premium and 140CRA312xxx when sending a specially crafted Modbus packet, which could cause a denial of service to the device that would force a restart to restore availability.
|
|||||
| CVE-2018-7762 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow.
|
|||||
| CVE-2018-7761 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
|
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.
|
|||||
| CVE-2018-7760 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
|
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization.
|
|||||
| CVE-2018-7759 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
|
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied.
|
|||||
| CVE-2018-7242 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 5.0 MEDIUM | 9.8 CRITICAL |
|
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks.
|
|||||
| CVE-2018-7241 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 10.0 HIGH | 9.8 CRITICAL |
|
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules.
|
|||||
| CVE-2015-6462 | 1 Schneider-electric | 22 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 19 more | 2024-11-21 | 3.5 LOW | 5.4 MEDIUM |
|
Reflected Cross-Site Scripting (nonpersistent) allows an attacker to craft a specific URL, which contains Java script that will be executed on the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC client browser.
|
|||||
| CVE-2015-6461 | 1 Schneider-electric | 22 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 19 more | 2024-11-21 | 5.5 MEDIUM | 5.4 MEDIUM |
|
Remote file inclusion allows an attacker to craft a specific URL referencing the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC web server, which, when launched, will result in the browser redirecting to a remote file via a Java script loaded with the web page.
|
|||||