CVE-2011-2530 1 Rockwellautomation 2 Eds Hardware Installation Tool, Rslinx 2025-04-11 9.3 HIGH N/A
Buffer overflow in RSEds.dll in RSHWare.exe in the EDS Hardware Installation Tool 1.0.5.1 and earlier in Rockwell Automation RSLinx Classic before 2.58 allows user-assisted remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a malformed .eds file.
CVE-2012-4713 1 Rockwellautomation 1 Factorytalk Services Platform 2025-04-11 7.8 HIGH N/A
Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a negative integer value.
CVE-2012-4715 1 Rockwellautomation 1 Rslinx Enterprise 2025-04-11 10.0 HIGH N/A
Buffer overflow in LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via a UDP packet with a certain integer length value that is (1) too large or (2) too small, leading to improper handling by Logger.dll.
CVE-2010-2965 2 Rockwellautomation, Windriver 3 1756-enbt\/a, 1756-enbt\/a Firmware, Vxworks 2025-04-11 10.0 HIGH N/A
The WDB target agent debug service in Wind River VxWorks 6.x, 5.x, and earlier, as used on the Rockwell Automation 1756-ENBT series A with firmware 3.2.6 and 3.6.1 and other products, allows remote attackers to read or modify arbitrary memory locations, perform function calls, or manage tasks via requests to UDP port 17185, a related issue to CVE-2005-3804.
CVE-2012-0222 1 Rockwellautomation 2 Factorytalk, Rslogix 5000 2025-04-11 5.0 MEDIUM N/A
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 allows remote attackers to cause a denial of service (out-of-bounds read) via a crafted packet.
CVE-2012-4690 1 Rockwellautomation 3 Ab Micrologix Controller, Plc-5 Controller, Slc 500 Controller 2025-04-11 7.1 HIGH N/A
Rockwell Automation Allen-Bradley MicroLogix controller 1100, 1200, 1400, and 1500; SLC 500 controller platform; and PLC-5 controller platform, when Static status is not enabled, allow remote attackers to cause a denial of service via messages that trigger modification of status bits.
CVE-2009-3739 1 Rockwellautomation 2 Ab Micrologix Controller 1100, Ab Micrologix Controller 1400 2025-04-11 10.0 HIGH N/A
Multiple unspecified vulnerabilities on the Rockwell Automation AB Micrologix 1100 and 1400 controllers allow remote attackers to obtain privileged access or cause a denial of service (halt) via unknown vectors.
CVE-2011-2957 1 Rockwellautomation 1 Factorytalk Diagnostics Viewer 2025-04-11 6.9 MEDIUM N/A
Unspecified vulnerability in Rockwell Automation FactoryTalk Diagnostics Viewer before V2.30.00 (CPR9 SR3) allows local users to execute arbitrary code via a crafted FactoryTalk Diagnostics Viewer (.ftd) configuration file, which triggers memory corruption.
CVE-2009-0472 1 Rockwellautomation 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge 2025-04-09 4.3 MEDIUM N/A
Multiple cross-site scripting (XSS) vulnerabilities in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allow remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2009-0473 1 Rockwellautomation 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge 2025-04-09 6.8 MEDIUM N/A
Open redirect vulnerability in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors.
CVE-2009-0474 1 Rockwellautomation 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge 2025-04-09 5.0 MEDIUM N/A
The web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to obtain "internal web page information" and "internal information about the module" via unspecified vectors. NOTE: this may overlap CVE-2002-1603.
CVE-2024-12672 2 Microsoft, Rockwellautomation 2 Windows, Arena 2025-04-03 N/A 7.3 HIGH
A third-party vulnerability exists in the Rockwell Automation Arena® that could allow a threat actor to write beyond the boundaries of allocated memory in a DOE file. If exploited, a threat actor could leverage this vulnerability to execute arbitrary code. To exploit this vulnerability, a legitimate user must execute the malicious code crafted by the threat actor.
CVE-2024-12175 1 Rockwellautomation 1 Arena 2025-03-13 N/A 7.8 HIGH
Another “use after free” code execution vulnerability exists in the Rockwell Automation Arena® that could allow a threat actor to craft a DOE file and force the software to use a resource that was already used. If exploited, a threat actor could leverage this vulnerability to execute arbitrary code. To exploit this vulnerability, a legitimate user must execute the malicious code crafted by the threat actor.
CVE-2024-11157 1 Rockwellautomation 1 Arena 2025-03-13 N/A 7.3 HIGH
A third-party vulnerability exists in the Rockwell Automation Arena® that could allow a threat actor to write beyond the boundaries of allocated memory in a DOE file. If exploited, a threat actor could leverage this vulnerability to execute arbitrary code. To exploit this vulnerability, a legitimate user must execute the malicious code crafted by the threat actor.
CVE-2024-2424 1 Rockwellautomation 2 5015-aenftxt, 5015-aenftxt Firmware 2025-02-25 N/A 7.5 HIGH
An input validation vulnerability exists in the Rockwell Automation 5015-AENFTXT that causes the secondary adapter to result in a major nonrecoverable fault (MNRF) when malicious input is entered. If exploited, the availability of the device will be impacted, and a manual restart is required. Additionally, a malformed PTP packet is needed to exploit this vulnerability.
CVE-2022-2848 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 5 more 2025-02-18 N/A 9.1 CRITICAL
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a heap-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-16 ...

Show More

CVE-2022-2825 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 5 more 2025-02-18 N/A 9.8 CRITICAL
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-1 ...

Show More

CVE-2024-37369 1 Rockwellautomation 1 Factorytalk View 2025-01-31 N/A 8.8 HIGH
A privilege escalation vulnerability exists in the affected product. The vulnerability allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system.
CVE-2024-37368 1 Rockwellautomation 1 Factorytalk View 2025-01-31 N/A 7.5 HIGH
A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.
CVE-2024-2427 1 Rockwellautomation 2 Powerflex 527 Ac Drives, Powerflex 527 Ac Drives Firmware 2025-01-31 N/A 7.5 HIGH
A denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper traffic throttling in the device. If multiple data packets are sent to the device repeatedly the device will crash and require a manual restart to recover.
CVE-2024-2426 1 Rockwellautomation 2 Powerflex 527 Ac Drives, Powerflex 527 Ac Drives Firmware 2025-01-31 N/A 7.5 HIGH
A denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper input validation in the device. If exploited, a disruption in the CIP communication will occur and a manual restart will be required by the user to recover it.
CVE-2024-2425 1 Rockwellautomation 2 Powerflex 527 Ac Drives, Powerflex 527 Ac Drives Firmware 2025-01-31 N/A 7.5 HIGH
A denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper input validation in the device. If exploited, the web server will crash and need a manual restart to recover it.
CVE-2024-7513 1 Rockwellautomation 1 Factorytalk View 2025-01-31 N/A 8.8 HIGH
CVE-2024-7513 IMPACT A code execution vulnerability exists in the affected product. The vulnerability occurs due to improper default file permissions allowing any user to edit or replace files, which are executed by account with elevated permissions.
CVE-2024-45824 1 Rockwellautomation 1 Factorytalk View 2025-01-31 N/A 9.8 CRITICAL
CVE-2024-45824 IMPACT A remote code vulnerability exists in the affected products. The vulnerability occurs when chained with Path Traversal, Command Injection, and XSS Vulnerabilities and allows for full unauthenticated remote code execution. The link in the mitigations section below contains patches to fix this issue.
CVE-2024-40620 1 Rockwellautomation 1 Pavilion8 2025-01-31 N/A 7.5 HIGH
CVE-2024-40620 IMPACT A vulnerability exists in the affected product due to lack of encryption of sensitive information. The vulnerability results in data being sent between the Console and the Dashboard without encryption, which can be seen in the logs of proxy servers, potentially impacting the data's confidentiality.
CVE-2024-40619 1 Rockwellautomation 4 Controllogix 5580, Controllogix 5580 Firmware, Guardlogix 5580 and 1 more 2025-01-31 N/A 7.5 HIGH
CVE-2024-40619 IMPACT A denial-of-service vulnerability exists in the affected products. The vulnerability occurs when a malformed CIP packet is sent over the network to the device and results in a major nonrecoverable fault causing a denial-of-service.
CVE-2024-6435 1 Rockwellautomation 1 Pavilion8 2025-01-31 N/A 8.8 HIGH
A privilege escalation vulnerability exists in the affected products which could allow a malicious user with basic privileges to access functions which should only be available to users with administrative level privileges. If exploited, an attacker could read sensitive data, and create users. For example, a malicious user with basic privileges could perform critical functions such as creating a user with elevated privileges and reading sensitive information in the “views” section.
CVE-2024-4609 1 Rockwellautomation 1 Factorytalk View 2025-01-30 N/A 9.8 CRITICAL
A vulnerability exists in the Rockwell Automation FactoryTalk® View SE Datalog function that could allow a threat actor to inject a malicious SQL statement if the SQL database has no authentication in place or if legitimate credentials were stolen. If exploited, the attack could result in information exposure, revealing sensitive information. Additionally, a threat actor could potentially modify and delete the data in a remote database. An attack would only affect the HMI design time, not runtim ...

Show More

CVE-2023-29029 1 Rockwellautomation 4 Armorstart St 281e, Armorstart St 281e Firmware, Armorstart St 284ee and 1 more 2025-01-24 N/A 4.7 MEDIUM
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.
CVE-2023-29028 1 Rockwellautomation 4 Armorstart St 281e, Armorstart St 281e Firmware, Armorstart St 284ee and 1 more 2025-01-24 N/A 4.7 MEDIUM
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.
CVE-2023-29027 1 Rockwellautomation 4 Armorstart St 281e, Armorstart St 281e Firmware, Armorstart St 284ee and 1 more 2025-01-24 N/A 4.7 MEDIUM
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.
CVE-2023-29026 1 Rockwellautomation 4 Armorstart St 281e, Armorstart St 281e Firmware, Armorstart St 284ee and 1 more 2025-01-24 N/A 4.7 MEDIUM
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.
CVE-2023-29022 1 Rockwellautomation 4 Armorstart St 281e, Armorstart St 281e Firmware, Armorstart St 284ee and 1 more 2025-01-24 N/A 4.7 MEDIUM
A cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.
CVE-2024-21913 1 Rockwellautomation 1 Arena 2024-12-17 N/A 7.8 HIGH
A heap-based memory buffer overflow vulnerability in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code into the software by overstepping the memory boundaries, which triggers an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threa ...

Show More

CVE-2024-21919 1 Rockwellautomation 1 Arena 2024-12-17 N/A 7.8 HIGH
An uninitialized pointer in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code to the software by leveraging the pointer after it is properly. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21912 1 Rockwellautomation 1 Arena 2024-12-17 N/A 7.8 HIGH
An arbitrary code execution vulnerability in Rockwell Automation Arena Simulation could let a malicious user insert unauthorized code into the software. This is done by writing beyond the designated memory area, which causes an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21918 1 Rockwellautomation 1 Arena 2024-12-17 N/A 7.8 HIGH
A memory buffer vulnerability in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code to the software by corrupting the memory and triggering an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-2929 1 Rockwellautomation 1 Arena 2024-12-17 N/A 7.8 HIGH
A memory corruption vulnerability in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code to the software by corrupting the memory triggering an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2023-27854 1 Rockwellautomation 1 Arena 2024-12-17 N/A 7.8 HIGH
An arbitrary code execution vulnerability was reported to Rockwell Automation in Arena Simulation that could potentially allow a malicious user to commit unauthorized arbitrary code to the software by using a memory buffer overflow.  The threat-actor could then execute malicious code on the system affecting the confidentiality, integrity, and availability of the product.  The user would need to open a malicious file provided to them by the attacker for the code to execute.
CVE-2023-27858 1 Rockwellautomation 1 Arena 2024-12-17 N/A 7.8 HIGH
Rockwell Automation Arena Simulation contains an arbitrary code execution vulnerability that could potentially allow a malicious user to commit unauthorized code to the software by using an uninitialized pointer in the application.  The threat-actor could then execute malicious code on the system affecting the confidentiality, integrity, and availability of the product.  The user would need to open a malicious file provided to them by the attacker for the code to execute.