CVE-2021-27430 1 Ge 1 Ur Bootloader Binary 2024-11-21 4.6 MEDIUM 8.4 HIGH
GE UR bootloader binary Version 7.00, 7.01 and 7.02 included unused hardcoded credentials. Additionally, a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR.
CVE-2021-27428 1 Ge 38 Multilin B30, Multilin B30 Firmware, Multilin B90 and 35 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade firmware without appropriate privileges. The weakness is assessed, and mitigation is implemented in firmware Version 8.10.
CVE-2021-27426 1 Ge 38 Multilin B30, Multilin B30 Firmware, Multilin B90 and 35 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
GE UR IED firmware versions prior to version 8.1x with “Basic” security variant does not allow the disabling of the “Factory Mode,” which is used for servicing the IED by a “Factory” user.
CVE-2021-27424 1 Ge 38 Multilin B30, Multilin B30 Firmware, Multilin B90 and 35 more 2024-11-21 5.0 MEDIUM 5.3 MEDIUM
GE UR firmware versions prior to version 8.1x shares MODBUS memory map as part of the communications guide. GE was made aware a “Last-key pressed” MODBUS register can be used to gain unauthorized information.
CVE-2021-27422 1 Ge 38 Multilin B30, Multilin B30 Firmware, Multilin B90 and 35 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
GE UR firmware versions prior to version 8.1x web server interface is supported on UR over HTTP protocol. It allows sensitive information exposure without authentication.
CVE-2021-27420 1 Ge 38 Multilin B30, Multilin B30 Firmware, Multilin B90 and 35 more 2024-11-21 5.0 MEDIUM 5.3 MEDIUM
GE UR firmware versions prior to version 8.1x web server task does not properly handle receipt of unsupported HTTP verbs, resulting in the web server becoming temporarily unresponsive after receiving a series of unsupported HTTP requests. When unresponsive, the web server is inaccessible. By itself, this is not particularly significant as the relay remains effective in all other functionality and communication channels.
CVE-2021-27418 1 Ge 38 Multilin B30, Multilin B30 Firmware, Multilin B90 and 35 more 2024-11-21 4.3 MEDIUM 5.3 MEDIUM
GE UR firmware versions prior to version 8.1x supports web interface with read-only access. The device fails to properly validate user input, making it possible to perform cross-site scripting attacks, which may be used to send a malicious script. Also, UR Firmware web server does not perform HTML encoding of user-supplied strings.
CVE-2020-6992 1 Ge 1 Cimplicity 2024-11-21 4.6 MEDIUM 6.7 MEDIUM
A local privilege escalation vulnerability has been identified in the GE Digital CIMPLICITY HMI/SCADA product v10.0 and prior. If exploited, this vulnerability could allow an adversary to modify the system, leading to the arbitrary execution of code. This vulnerability is only exploitable if an attacker has access to an authenticated session. GE Digital CIMPLICITY v11.0, released January 2020, contains mitigation for this local privilege escalation vulnerability. GE Digital recommends all users ...

Show More

CVE-2020-6977 1 Ge 32 Invenia Abus Scan Station, Invenia Abus Scan Station Firmware, Logiq E10 and 29 more 2024-11-21 7.2 HIGH 6.8 MEDIUM
A restricted desktop environment escape vulnerability exists in the Kiosk Mode functionality of affected devices. Specially crafted inputs can allow the user to escape the restricted environment, resulting in access to the underlying operating system. Affected devices include the following GE Ultrasound Products: Vivid products - all versions; LOGIQ - all versions not including LOGIQ 100 Pro; Voluson - all versions; Versana Essential - all versions; Invenia ABUS Scan station - all versions; Venu ...

Show More

CVE-2020-36549 1 Ge 2 Voluson S8, Voluson S8 Firmware 2024-11-21 7.2 HIGH 8.8 HIGH
A vulnerability classified as critical was found in GE Voluson S8. Affected is the underlying Windows XP operating system. Missing patches might introduce an excessive attack surface. Access to the local network is required for this attack to succeed.
CVE-2020-36548 1 Ge 2 Voluson S8, Voluson S8 Firmware 2024-11-21 7.2 HIGH 5.9 MEDIUM
A vulnerability classified as problematic has been found in GE Voluson S8. Affected is the file /uscgi-bin/users.cgi of the Service Browser. The manipulation leads to improper authentication and elevated access possibilities. It is possible to launch the attack on the local host.
CVE-2020-36547 1 Ge 2 Voluson S8, Voluson S8 Firmware 2024-11-21 7.2 HIGH 5.9 MEDIUM
A vulnerability was found in GE Voluson S8. It has been rated as critical. This issue affects the Service Browser which itroduces hard-coded credentials. Attacking locally is a requirement. It is recommended to change the configuration settings.
CVE-2020-27267 4 Ge, Ptc, Rockwellautomation and 1 more 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more 2024-11-21 6.4 MEDIUM 9.1 CRITICAL
KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server all 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data.
CVE-2020-27265 4 Ge, Ptc, Rockwellautomation and 1 more 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and remotely execute code.
CVE-2020-27263 4 Ge, Ptc, Rockwellautomation and 1 more 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more 2024-11-21 6.4 MEDIUM 9.1 CRITICAL
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data.
CVE-2020-25197 1 Ge 6 Rt430, Rt430 Firmware, Rt431 and 3 more 2024-11-21 9.0 HIGH 9.8 CRITICAL
A code injection vulnerability exists in one of the webpages in GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06 that could allow an authenticated remote attacker to execute arbitrary code on the system.
CVE-2020-25193 1 Ge 6 Rt430, Rt430 Firmware, Rt431 and 3 more 2024-11-21 5.0 MEDIUM 5.3 MEDIUM
By having access to the hard-coded cryptographic key for GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06, attackers would be able to intercept and decrypt encrypted traffic through an HTTPS connection.
CVE-2020-16246 1 Ge 4 S2020, S2020 Firmware, S2024 and 1 more 2024-11-21 4.3 MEDIUM 6.1 MEDIUM
The affected Reason S20 Ethernet Switch is vulnerable to cross-site scripting (XSS), which may allow attackers to trick users into following a link or navigating to a page that posts a malicious JavaScript statement to the vulnerable site, causing the malicious JavaScript to be rendered by the site and executed by the victim client.
CVE-2020-16244 1 Ge 1 Asset Performance Management Classic 2024-11-21 4.0 MEDIUM 7.2 HIGH
GE Digital APM Classic, Versions 4.4 and prior. Salt is not used for hash calculation of passwords, making it possible to decrypt passwords. This design flaw, along with the IDOR vulnerability, puts the entire platform at high risk because an authenticated user can retrieve all user account data and then retrieve the actual passwords.
CVE-2020-16242 1 Ge 4 S2020, S2020 Firmware, S2024 and 1 more 2024-11-21 4.3 MEDIUM 6.1 MEDIUM
The affected Reason S20 Ethernet Switch is vulnerable to cross-site scripting (XSS), which may allow an attacker to trick application users into performing critical application actions that include, but are not limited to, adding and updating accounts.
CVE-2020-16240 1 Ge 1 Asset Performance Management Classic 2024-11-21 5.0 MEDIUM 5.3 MEDIUM
GE Digital APM Classic, Versions 4.4 and prior. An insecure direct object reference (IDOR) vulnerability allows user account data to be downloaded in JavaScript object notation (JSON) format by users who should not have access to such functionality. An attacker can download sensitive data related to user accounts without having the proper privileges.
CVE-2020-12017 1 Ge 6 Rt430, Rt430 Firmware, Rt431 and 3 more 2024-11-21 9.0 HIGH 9.8 CRITICAL
GE Grid Solutions Reason RT Clocks, RT430, RT431, and RT434, all firmware versions prior to 08A05. The device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated attacker to execute arbitrary commands and send a request to a specific URL that could cause the device to become unresponsive. The unauthenticated attacker may change the password of the 'configuration' user account, allowing ...

Show More

CVE-2019-6566 1 Ge 1 Ge Communicator 2024-11-21 7.2 HIGH 7.8 HIGH
GE Communicator, all versions prior to 4.0.517, allows a non-administrative user to replace the uninstaller with a malicious version, which could allow an attacker to gain administrator privileges to the system.
CVE-2019-6564 1 Ge 1 Ge Communicator 2024-11-21 6.9 MEDIUM 7.8 HIGH
GE Communicator, all versions prior to 4.0.517, allows a non-administrative user to place malicious files within the installer file directory, which may allow an attacker to gain administrative privileges on a system during installation or upgrade.
CVE-2019-6548 1 Ge 1 Ge Communicator 2024-11-21 6.8 MEDIUM 9.8 CRITICAL
GE Communicator, all versions prior to 4.0.517, contains two backdoor accounts with hardcoded credentials, which may allow control over the database. This service is inaccessible to attackers if Windows default firewall settings are used by the end user.
CVE-2019-6546 1 Ge 1 Ge Communicator 2024-11-21 6.8 MEDIUM 7.8 HIGH
GE Communicator, all versions prior to 4.0.517, allows an attacker to place malicious files within the working directory of the program, which may allow an attacker to manipulate widgets and UI elements.
CVE-2019-6544 1 Ge 1 Ge Communicator 2024-11-21 6.8 MEDIUM 5.6 MEDIUM
GE Communicator, all versions prior to 4.0.517, has a service running with system privileges that may allow an unprivileged user to perform certain administrative actions, which may allow the execution of scheduled scripts with system administrator privileges. This service is inaccessible to attackers if Windows default firewall settings are used by the end user.
CVE-2019-18267 1 Ge 4 S2020, S2020 Firmware, S2020g and 1 more 2024-11-21 3.5 LOW 5.4 MEDIUM
An issue was found in GE S2020/S2020G Fast Switch 61850, S2020/S2020G Fast Switch 61850 Versions 07A03 and prior. An attacker can inject arbitrary Javascript in a specially crafted HTTP request that may be reflected back in the HTTP response. The device is also vulnerable to a stored cross-site scripting vulnerability that may allow session hijacking, disclosure of sensitive data, cross-site request forgery (CSRF) attacks, and remote code execution.
CVE-2019-18255 1 Ge 1 Ifix 2024-11-21 2.1 LOW 5.5 MEDIUM
HMI/SCADA iFIX (Versions 6.1 and prior) allows a local authenticated user to modify system-wide iFIX configurations through section objects. This may allow privilege escalation.
CVE-2019-18243 1 Ge 1 Ifix 2024-11-21 2.1 LOW 5.5 MEDIUM
HMI/SCADA iFIX (Versions 6.1 and prior) allows a local authenticated user to modify system-wide iFIX configurations through the registry. This may allow privilege escalation.
CVE-2019-13559 1 Ge 1 Mark Vie Controll System 2024-11-21 7.2 HIGH 7.8 HIGH
GE Mark VIe Controller is shipped with pre-configured hard-coded credentials that may allow root-user access to the controller. A limited application of the affected product may ship without setup and configuration instructions immediately available to the end user. The bulk of controllers go into applications requiring the GE commissioning engineer to change default configurations during the installation process. GE recommends that users reset controller passwords during installation in the ope ...

Show More

CVE-2019-13554 1 Ge 1 Mark Vie Control System 2024-11-21 6.5 MEDIUM 8.8 HIGH
GE Mark VIe Controller has an unsecured Telnet protocol that may allow a user to create an authenticated session using generic default credentials. GE recommends that users disable the Telnet service.
CVE-2019-10966 1 Ge 8 Aespire 7100, Aespire 7100 Firmware, Aespire 7900 and 5 more 2024-11-21 5.0 MEDIUM 5.3 MEDIUM
In GE Aestiva and Aespire versions 7100 and 7900, a vulnerability exists where serial devices are connected via an added unsecured terminal server to a TCP/IP network configuration, which could allow an attacker to remotely modify device configuration and silence alarms.
CVE-2018-8867 1 Ge 16 Pacsystems Cpu320, Pacsystems Cpu320 Firmware, Pacsystems Cru320 and 13 more 2024-11-21 7.8 HIGH 7.5 HIGH
In GE PACSystems RX3i CPE305/310 version 9.20 and prior, RX3i CPE330 version 9.21 and prior, RX3i CPE 400 version 9.30 and prior, PACSystems RSTi-EP CPE 100 all versions, and PACSystems CPU320/CRU320 RXi all versions, the device does not properly validate input, which could allow a remote attacker to send specially crafted packets causing the device to become unavailable.
CVE-2018-5475 1 Ge 2 D60 Line Distance Relay, D60 Line Distance Relay Firmware 2024-11-21 7.5 HIGH 9.8 CRITICAL
A Stack-based Buffer Overflow issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. Multiple stack-based buffer overflow vulnerabilities have been identified, which may allow remote code execution.
CVE-2018-5473 1 Ge 2 D60 Line Distance Relay, D60 Line Distance Relay Firmware 2024-11-21 10.0 HIGH 9.8 CRITICAL
An Improper Restriction of Operations within the Bounds of a Memory Buffer issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. The SSH functions of the device are vulnerable to buffer overflow conditions that may allow a remote attacker to execute arbitrary code on the device.
CVE-2018-19003 1 Ge 6 Ex2100e, Ex2100e Firmware, Ls2100e and 3 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
GE Mark VIe, EX2100e, EX2100e_Reg, and LS2100e Versions 03.03.28C to 05.02.04C, EX2100e All versions prior to v04.09.00C, EX2100e_Reg All versions prior to v04.09.00C, and LS2100e All versions prior to v04.09.00C The affected versions of the application have a path traversal vulnerability that fails to restrict the ability of an attacker to gain access to restricted information.
CVE-2018-17925 1 Ge 1 Ifix 2024-11-21 4.4 MEDIUM 4.8 MEDIUM
Multiple instances of this vulnerability (Unsafe ActiveX Control Marked Safe For Scripting) have been identified in the third-party ActiveX object provided to GE iFIX versions 2.0 - 5.8 by Gigasoft. Only the independent use of the Gigasoft charting package outside the iFIX product may expose users to the reported vulnerability. The reported method shown to impact Internet Explorer is not exposed in the iFIX product, nor is the core functionality of the iFIX product known to be impacted.
CVE-2018-15362 1 Ge 1 Cimplicity 2024-11-21 6.4 MEDIUM 9.1 CRITICAL
XXE in GE Proficy Cimplicity GDS versions 9.0 R2, 9.5, 10.0
CVE-2018-10615 1 Ge 1 Mds Pulsenet 2024-11-21 6.5 MEDIUM 8.1 HIGH
Directory traversal may lead to files being exfiltrated or deleted on the GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior host platform.